  • 1 HIVERT-Y(T)VF
  • 2 vector control, energy feedback technology
  • 3 Used predominantly in mining and related industries

 

Control Theory

Hiconics manufactures two models of four quadrant MV VFDs for use with mining hoists. The HIVERT-YVF (for asynchronous motor) and HIVERT-TVF (for synchronous motor) are both composed of a transformer, a power cell and a control system (including controller, I/O board and HMI). When the VFD applies for motor power exceeding 1800kw, the system will add start cabinet to the supply.

 

 

 

Power Cell

The power cell input connects with the reactor and the transformer secondary winding three-phase low voltage output. When the VFD power is below 1800kw, the power cell adds cushion protection to limit pre-charge current and protect the IGBT input. When the VFD power goes above 1800kw, the system will cancel the power cell cushion and the start cabinet will limit the pre-charge current and protect the IGBT input. The power cell and reactor directly connect. The HIVERT-Y(T)VF is 100% rated power energy feedback capacity. The power cell uses a IGBT rectifier which inspects the power cell input voltage amplitude and phase. It then controlls the phase difference between the IGBT and the power cell input voltage to determine the direction betweenthe  grid and the power cell. If the power cell phase is front, the power cell will return power to grid. Otherwise, the grid will send power to the power cell. Electricity power is decided by power cell voltage. If the rectifier is acting as power, the phase difference will be from power voltage value and actual voltage value, PID adjustment.

The HIVERT-Y(T)VF is  a new Hiconics product used for synchronous and asynchronous AC drive motors. It makes use of the most up to date power cell connection technology, vector control, inverter energy feedback technololy, all in one inproved HMI operation system. This allows for higher reliability and excellent performance. It is exclusively for users who want to equip their motor with four quandrant, energy feedback, low speed, high torque drive. It is currently widely used in Chinese mining, often with motors running hoists and conveyors.

 

Key features:

Advantages over other MV VFDs:

• Power cell connection and output wave, configured in as 6kv, 6 power cell per phase, reduce the harmonic distrotion

• No filter device at input and output side

• It is possible to use ynchronous and asycnhronous motors without increasing motor temperature

• No limit to the cables within the voltage loss range

• Prevents dv/dt damage

• Eliminates pulse torque from harmony, extending motor sevice time

• The motor will not derate due to harmony

 

Friendly HMI operation:

• HIVERT display and buttons available in both English and Chinese

• HMI can set up exact and accurate parameters without code

• Running parameters are displayed in the HMI.

• 10 record for fault including position, time, reason

 

Other:

• High reliability, rated load, system efficiency of more than 96%, VFD efficiency of more than 98%

• Power cells designed for easy to replacement and maintenance.

• Power cell cable communication completely electronics isolation

• Internal PID adjustment makes it possible to close loop runing

• Communication choice  RS485,standard MODBUS RTU; PROFIBUS DP optional

• Control mode equiped with local, remote and upper systems

• Fault inspection circuit has fault alarm  and protection system, issues complete fault record

• Compact structure 

• Possible to adapt design to different applications

1、Model 

 2、Spec 

Motor

Power

Output Capacity

Model

Weight(kg)

Dimension(W×H×D)

Cabinet

Asychronous

315kW

400kVA

HIVERT-YVF 06/048

3150

2100×2300×1400

FC1

400kW

500kVA

HIVERT-YVF 06/061

3400

500kW

630kVA

HIVERT-YVF 06/077

4376

4250×2200×1210

FC2

630kW

800kVA

HIVERT-YVF 06/096

4686

800kW

1000kVA

HIVERT-YVF 06/130

5016

1000kW

1250kVA

HIVERT-YVF 06/154

7630

5200×2100×1210

FC4

1250kW

1600kVA

HIVERT-YVF 06/192

8310

1400kW

1800kVA

HIVERT-YVF 06/220

9035

1600kW

2000kVA

HIVERT-YVF 06/243

9255

1800kW

2250kVA

HIVERT-YVF 06/273

12770

7645×2400×1410

FC5

2000kW

2500kVA

,HIVERT-YVF 06/304

13250

Synchronous

1250kW

1600kVA

HIVERT-TVF 06/192

8310

5200×2100×1210

FC4

1400kW

1800kVA

HIVERT-TVF 06/220

9035

1600kW

2000kVA

HIVERT-TVF 06/243

9255

1800kW

2250kVA

HIVERT-TVF 06/273

12770

7645×2400×1400

FC5

2000kW

2500kVA

HIVERT-TVF 06/304

13250

2500kW

3150kVA

HIVERT-TVF 06/400

13930

3200kW

4000kVA

HIVERT-TVF 06/500

15010

4500kW

kVA

HIVERT-TVF 06/600

22750

11875×2400×1410

FC6

  

 

3. Paramters

HIVERT-Y(T)VF is equiped with standard 6kV , can be equiped with other voltages according to customer requirements.

 
Model
HIVERT-TVF 06/X
Capacity(kVA)
315-5625kVA
Motor Power
  250-4500kW
Input Voltage(kV)
  6/10
Output Current (A)
61-600
Output Voltage(kV)
 6
Power cell qty per phase
 6
Input Frequency
 45Hz~55Hz
Input Voltage
 6/10kV(-20%~15%)
Technology
vector control with speed sensor
Power Control
 380VAC
Input Power Factor
rated load>0.96
Efficiency(including transormer)
rated load>96%
Output Frequency Range
 0Hz to 120Hz
Resolution Frequency 
 0.01Hz(0-80Hz);0.02(80-120Hz)
Over Load
 120%, 2 min; 150%, protection
Analog Input
2 loop, 4~20mA
Analog Output
4 loop, 4~20mA
Communication
 RS485
acce/dece time
5s~1600s
DI  input and output
 12 input /9 output
Ambient Temperature
 -5 to 45℃
Stock Condition
 -40 to 70℃
Cooling System
 AN
Humidity
 <90%, no condensity
      Altititude

 <1000m, for every additional 100 m beyond 1000 m 1% derating is required

   Heat(KW)

not mto exceed 4% rated power 

 

•Control theory

Hiconics manufactures two models of four quadrant MV VFDs for use with mining hoists: the HIVERT-YVF (for asynchronous motor) and HIVERT-TVF (for synchronous motor). They are both composed of a transformer, a power cell and a control system (including controller, I/O board and HMI).

 

•Start cabinet

When the VFD applies for motor power exceeding 1800kw, the system will add start cabinet in the supply. The start cabinet can restrain the exciting current when the transformer is turned on to allow power cabinet protection. It is also possible to simultaneou charge to the DC capacitor power cell. The start cabinet is equipped with start resistance which reduces the rush current when the drive is turned on. Different power VFDs will use different start resistances and after pre-charge the VCB will short circuit the resistance.

 

•Transformer

A dry type isolation transformer, using a air forced cooling system, is the primary start connection. It allows a connection to the grid or start cabinet. A secondary winding is extended triangle connection, there is phase difference between windings, through reactor to supply power for the power cells.

The transformer is equipped with a temperature controller, which the control system uses to inspect the transformer temperature. When the winding temperature is high, the system alarm will be triggered and start the bottom fans. 

 

•Power cell

The power cell input connects with the reactor and the transformer secondary winding three-phase low voltage output. When the VFD power drops below 1800kw, the power cell adds cushion protection to limit the pre-charge current and protect the IGBT input. When the VFD power rises above 1800kw, the cancel power cell cushion and start cabinet will limit pre-charge current and protect IGBT input. The power cell and reactor will then directly connect. The HIVERT-Y(T)VF product is 100% rated power energy feedback capacity. The power cell uses an IGBT rectifier which inspects the power cell input voltage amplitude and phase. It controlls the phase difference between the IGBT and the power cell input voltage to deterine the direction between the grid and the power cell. If the power cell phase is front, the power cell will return the power to grid, otherwise, the grid will send power to the power cell. Electricity power is decided by the power cell voltage. If the rectifier side is acting as a power source the phase difference will be from power voltage value and actual voltage value, PID adjustment.

 

•Control system

The control system is composed of a controller, an HMI, and an I/O board. The HIVERT-YVF uses rotor with speed feedback vector control technology. The rotor magnetic field positioning coordinate divides the motor rotor current  into exciting current and torque current. Keep exciting current iM invariant, control torque current controlls the motor torque. Motor speed uses close loop control. When running, the set speed and actual speed variance is adjustable by PID to make iT. iM and iT with actual feedback exciting current iM and torque current iT, normally after PI adjustment, will make uM,uT, after vector control, it will make voltage drive signal.

CONTROLLER

I/O BOARD